← Home

Plant assets

Plant · updated 2026-08-07 · 133 assets

Tree of major equipment. 2026-08-07 intake wave: compressors, vacuum, feedwater, reheat pumps, domestic booster, quench tank, receiver, dryer vessels, AHU-2 motor, Cemline actuators, REF-14 VFD, ice machine; AHU VFD enclosure ACs AC1/AC2 (McLean HB16).

AHU-1-CC2 · coil

Cooling coil B (CC-2)

York CDW chilled-water coil B of 3 on AHU-1 — ~100 tons design each.

Identity

Position
Coil B / CC-2 on AHU-1
Manufacturer
York YORKCOIL
Type
CDW chilled-water, loose coil
Quantity in bank
1 of 3 identical

Geometry

Rows × FPI
8 × 9
Tubes
5/8" stainless steel
Fins
Aluminum
Finned length × height
134" × 39.25"
Connection
3"
Fluid volume
35 gal
Weight
1,026 lb

Air side (design)

CFM
18,334
Face velocity
501 fpm
EAT
91°F DB / 73°F WB
LAT
53.3°F DB / 52.9°F WB
Air PD
1.05 in.wg

Water side (design)

EWT → LWT
45°F → 55°F (10° ΔT)
GPM
241
Velocity
5.7 fps
Water PD
25.8 ft

Capacity

Total
1,203.3 MBH ≈ 100.3 tons
Sensible
755.8 MBH
Latent (approx)
~447 MBH

Children