CH-2 · chiller

Chiller #2

Trane Agility HDWA200 — 250 ton VFD centrifugal, R-513A. Nameplate photo 2026-08-07 (plant #2; intake note said #1 in error).

Identity

Plant tag
Chiller #2
Mfr model
HDWA200
Mfr sheet tag
CH-1 on selection (plant's #2)
Type
Centrifugal, 460 V VFD (Trane Agility)
Serial No.
L23A00088
S.O. No.
MLQ732A
AED model
AFT0315FAEA00D2B00
AED part No.
493/5000017
Date of mfg
25-01-24
Note
TOPSS selection + unit nameplate (photo intake)

Nameplate (unit)

Nameplate voltage
460 V, 3ø 60 Hz
Nameplate kW
156 kW
RLA
224 A
Line current range
414–506 VAC
MCA
279 A
Max overcurrent protective device
450 A
Short circuit current rating
65,000 A
Compressor motor
115 V AC / 60 Hz / 1 ph / RLA 315 / 3000 VA max
Factory charge
525 lb of R-513A
Field charge
0 lb of R-513A
Max refrigerant working pressure
HI side 300 psig · LO side 200 psig
Factory test pressure
HI side 330 psig · LO side 260 psig

Capacity / efficiency

Tons
250.00
Full-load kW/ton
0.6235
IPLV / NPLV
0.3929 / 0.3425 kW/ton

Electrical (full load)

Primary power
155.9 kW (nameplate 156 kW)
Primary RLA
224.3 A (nameplate 224 A)
LRA
850 A
MOCP / MCA
450 A / 279 A
Motor speed (full load)
23,000 rpm

Evaporator (CHW)

Design flow
597.4 GPM (2.39 gpm/ton)
Design temps
55°F EWT → 45°F LWT (10° ΔT)
Flow range
166.6 – 941.5 GPM
Refrigerant sat
43.6°F
Fouling
0.0001

Condenser (tower water)

Design flow
750 GPM (3.0 gpm/ton)
Design temps
85°F EWT → 94.47°F LWT
Flow range
339.1 – 1181.6 GPM
Refrigerant sat
96.79°F
Fouling
0.00025

Refrigerant

Type
R-513A
Charge
525 lb (factory, nameplate)
Operating weight
11,521 lb

Protection

Condenser pressure limit
93% of HPC (soft unload before hard trip)
Example live
118.5 psig / 94°F sat condensing

Field calibration

Point 1
98 kW @ 68% RLA
Point 2 (nameplate)
155.9 kW @ 100% RLA
Affine fit
kW ≈ 1.81·RLA% − 25 (clamped ≥0)

Notes

  • Nameplate photo intake 2026-08-07 (batch 20260807-122833-60f628c8). Upload note said "Chiller 1 if needed"; Clay corrected to plant Chiller #2.