← Home

Plant assets

Plant · updated 2026-08-07 · 133 assets

Tree of major equipment. 2026-08-07 intake wave: compressors, vacuum, feedwater, reheat pumps, domestic booster, quench tank, receiver, dryer vessels, AHU-2 motor, Cemline actuators, REF-14 VFD, ice machine; AHU VFD enclosure ACs AC1/AC2 (McLean HB16).

AC2-AHU2-VFD · equipment

VFD enclosure AC (AC2)

Dedicated air conditioner cooling the ahu2-vfd enclosure (plant label ac2-ahu2-vfd). Separate from the VFD's own 10×30 fan filter.

Identity

Plant tag
ac2-ahu2-vfd
Mfr
APW McLean
Type
Electronic enclosure air conditioner
Model
HB16-0916-013E
Serial No.
03010872-2
Serves
ahu2-vfd enclosure cooling only

Electrical

Volts
115 V
Hertz
60
Phase
1
F.L.A.
20.3 A

Refrigerant

Charge
22 oz / 624 g

Pressures

High
450 PSIG
Low
150 PSIG

Capacity

Cooling
9000 BTU / 2637 W

Ambient

Min/Max temp
50/125 °F (10/52 °C)

Enclosure

NEMA
Type 12
Use
Special purpose air conditioner — interface to electronic enclosure only; time-delay fuse or circuit breaker

Intake filter

Filter
EZ Kleen washable aluminum mesh
Actual size
15.25" × 14.75" × 13/16"
Qty
1
SKU
15.25x14.75x0.8125-WASH
Inventory asset
AC2-AHU2-VFD
Mfr part
10-1000-08 proposed — not confirmed; omitted from inventory SKU

Notes

  • Nameplate photo intake 2026-08-07 (batch 20260807-180827-c19416d7).
  • This is the dedicated AC that cools ahu2-vfd — washable filter is on this unit, not on the VFD fans.
  • Inventory asset AC2-AHU2-VFD (not bare AC-2; avoids clash with RTU AC-2).