← Home

Plant assets

Plant · updated 2026-08-07 · 133 assets

Tree of major equipment. 2026-08-07 intake wave: compressors, vacuum, feedwater, reheat pumps, domestic booster, quench tank, receiver, dryer vessels, AHU-2 motor, Cemline actuators, REF-14 VFD, ice machine; AHU VFD enclosure ACs AC1/AC2 (McLean HB16).

HV-4 · ahu

HV-4 (H&V-4)

Heating & ventilating unit — 20,000 CFM steam coil make-up into the boiler room.

Identity

Tag
HV-4 / H&V-4
Location
Fresh-air make-up into boiler room
Duty
Steam heating / ventilating of OA

Airflow

Design CFM
20,000 SCFM
Face velocity (coil)
709 fpm
Air PD (coil)
0.40 in.wg

Steam coil

Manufacturer
Marlo (AirFlow Equipment submittal 10/21/2002)
Model
(1) 2H21-84-8905T-28.2-H/V-B/W
Certification
ARI Std 410
Inlet
Single-end steam
Quantity
1 coil
Face
47.25 in H × 84.0 in L finned; face area 28.2 ft²
Tubes
Copper 0.035 in wall
Fins
Aluminum 0.010 in

Coil performance (design)

EAT → LAT
−10.0°F → 79.4°F DB
Sensible capacity
1,716,212 BTU/hr (~1.72 MMBTU/h)
Steam
10.0 psig / 239°F
Condensate
2,033 lb/hr

Blower

Type
BAF-DW size 300, DWDI Class I, 30" wheel
CFM @ SP
20,000 CFM @ 3.75 in.wg
RPM / tip speed
1,171 RPM / 9,197 fpm
Operating BHP
15.56 (motor ≥ 15.56 → likely 20 HP)
Outlet velocity
2,148 fpm (outlet area 15.56 ft²)
Static / mech eff
75.78% / 81.60%
Drive
Belt (sheave adjustable)
Max Class I RPM
1,349
Sound LwA
94 dB

Belts

Size
5VX900 (90 in)
Quantity
2

BMS

Points
HV4DaTemp, MaTemp, RmTemp, DaStpt, …

Notes

  • Fed from 10 psig plant steam (same header as HHW HX and Cemline).

Children