← Home

Plant assets

Plant · updated 2026-08-07 · 133 assets

Tree of major equipment. 2026-08-07 intake wave: compressors, vacuum, feedwater, reheat pumps, domestic booster, quench tank, receiver, dryer vessels, AHU-2 motor, Cemline actuators, REF-14 VFD, ice machine; AHU VFD enclosure ACs AC1/AC2 (McLean HB16).

RTU-1 · rtu

RTU-1 (HVAC-1)

Daikin DPSC10B 10-ton packaged rooftop — gas heat + DX, VAV, BACnet MS/TP. Standalone from EBI chiller plant.

Identity

Model
Daikin DPSC10B
Schedule tag
HVAC-1 / RTU-1
Mounting
Roof curb
Controls
MicroTech + BACnet MS/TP
Full model string
DPSC10BPB4AA0E45BEGH0E40CER0
Serial No.
E037574200100
GOI number
SLPU250525053
Form No.
910428287
Assembled
Mexico

Capacity

Design cooling
128,110 BTU/hr (~10.7 t)
Net capacity
121,000 BTU/hr
EER / IEER
11.9 / 20.2
Airflow
4,000 CFM

Physical

Dims
101.6" L × 73.4" W × 85.9" H
Weight
2,324 lb
Liner
1" injected foam R-7

Electrical

Service
460 V / 60 Hz / 3-ph
FLA / MCA / MROPD
28.9 A / 32.8 A / 45 A
SCCR
65 kAIC
MCA / MOP
33 A / 45 A

DX cooling

Coil
Cu/Al, 4 rows, 15 FPI, 15.4 ft² face
Refrigerant
R-32
Compressor
Inverter scroll, FLA 15.9 A
Condenser
Microchannel Al, 23 FPI; 2 condenser fans
Total power (mod)
8.18 kW
Circuit #1 charge
13.3 lb (6.0 kg)

Gas heat

Input / output
300 MBH / 243,000 BTU/hr
HX
Stainless, 5:1 modulating
Gas connection
3/4" FNPT, 5–14 in.w.c.

Fans

Supply
SWSI airfoil ECM, 18" wheel, 4,000 CFM, 1.2 in TSP, 2.4 BHP / 1.25 HP, 1547 rpm, direct drive
Exhaust
Airfoil power exhaust ECM, 16" wheel, 1.09 BHP, 1913 rpm

Filters

Factory
6 × 18×24×2 MERV 8
Spec note
Replace with MERV 11 2" pleated per filter schedule / spec

Notes

  • Not on Honeywell EBI All-Points XPS — BACnet only.
  • Nameplate photo intake 2026-08-07 (batch 20260807-125158-892ce551) — confirms HVAC-1 tag = plant RTU-1.

Children